Daylight Window

Design status and field checks

The Blender project verifies nominal geometry. The wall, electrical installation, thermal performance and building approvals are pending. This fixture provides decorative lighting only. It provides neither emergency escape nor ventilation.

Item Model assumption or check Field evidence still needed
Wall Two continuous studs at 16 in O.C. with 1.50 in members give a nominal 14.50 in clear bay. The 13.25 in body leaves 0.625 in nominal clearance each side before accounting for obstructions. Measure the actual clear bay width and depth at several heights, inspect structure, wiring and plumbing, and identify insulation, air/vapor and moisture layers. The recess needs independent verification.
Drywall and trim 0.50 in drywall. Concept drywall opening 13.50 × 49.75 in leaves 0.125 in around the body and 1.375 in nominal casing overlap per edge. The lower edge of the casing is 32 in above the floor. Check existing drywall thickness, floor level, available height, actual wall flatness, fastener substrate and clearances.
Acrylic Two independent 3 mm inserts. Nominal model envelope for each insert is about 11.50 × 23.45 in. Sight opening is 10.75 × 23.125 in each. Measure the finished retainer pockets. Confirm allowance for thermal expansion, material thickness, screw placement and removal clearance. Cut after a dry fit.
Enclosure 2.50 in body, 0.625 in casing, 1.718 in from LED tape face to inside acrylic face. Surface body finishes at approximately 3.125 in from wall to front casing. Validate mechanical attachment, service approach, heat-spreading section, materials and any ventilation path.
Power Four nominal 45 in runs in parallel total 4.572 m. At the brief's 16 W/m sizing assumption, the load is about 73 W DC or 3.05 A at 24 V before design margin. Confirm manufacturer data for the exact SKU, warm/cool and simultaneous current, combined limit, wiring route, wire size, protection, equipment suitability and sustained temperatures. Actual power draw is unmeasured.
Remote power Wiring diagram keeps mains PSU and controller in an accessible and ventilated location outside the concealed cavity. The room renders omit a specific field cable route. Review the equipment location and low-voltage route with the installer. Confirm the applicable rules with the local authority and a qualified electrical professional.
Sleeping room The model is a generic visualization. Verify the actual room's existing ventilation, emergency escape provisions and sleeping-room requirements before installation or use as a bedroom.
Daylight sensor One I²C sensor views daylight at an existing living-room window. The simulated day includes an afternoon cloud layer. Calibrate output against real observations. Record saturation, nuisance artificial light, stale readings, time response and night thresholds.

Aiming at a repeatable patch of sky through the existing window makes the sensor's reading a proxy for daylight at that location. Glass, shading, direction and room lights can all affect it. The acrylic shader and area lights simulate the design intent. Bench testing determines uniformity, delivered light and operating temperature.